PBT Gel-Filled Tube Temperature Sensing Cable

PBT Gel-Filled Tube Temperature Sensing Cable
Application scenarios
  • Suitable for temperature and pressure sensing. Structure: bare fiber + gel + PBT gel-filled tube + Kevlar + sheath.
  • Suitable for subway, tunnel, fire protection and other industries, avoiding disasters and safety accidents through temperature sensing.
Product features
  • All-dielectric structure design, combining excellent transmission performance with environmental adaptability.
  • Protected by a PBT tube, offering the advantages of light weight, small outer diameter, high strength and good water blocking.
  • Sealed process, eco-friendly and flame-retardant, providing water blocking and oil resistance.
Color identification
  • (1) Fiber colors (corresponding to 1-12 fibers)
  • Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Purple, Pink, Light Blue
  • (2) Cable colors (corresponding to 1-12)
  • Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Purple, Pink, Light Blue
  • Note: The outer sheath of the standard PBT gel-filled tube temperature sensing cable is blue by default.
Environmental certifications
  • Compliant with EU RoHS and REACH certification standards.
Structural dimensions
Item Unit Specification One-side thickness (mm)
Fiber mm 0.25±0.005 -
PBT tube mm 2.00±0.10 0.45
Kevlar fibers mm 2.20±0.10 -
Cable outer sheath mm 4.00±0.20 0.90
Cable weight Kg/km 25 -
Fiber performance
  • (1) Geometric characteristics
Test item MM 50 MM 62.5
Mode field diameter (mm) 50±2.5 62.5±2.5
Cladding diameter (mm) 124.8±1.0 124.8±1.0
Cladding non-circularity (%) ≤1.0 ≤1.0
Core-cladding concentricity error (mm) ≤1.5 ≤1.5
Coating diameter (mm) 245±7 245±7
Outer coating-cladding concentricity error (mm) ≤12.0 ≤12.0
  • (2) Optical characteristics
Test item MM 50 MM 62.5
Zero-dispersion wavelength λ0 (nm) 1295-1320 1320-1365
Zero-dispersion slope S0 (ps/(nm².km)) ≤0.101 ≤0.097
Effective group index (850nm) 1.481 1.496
Effective group index (1300nm) 1.476 1.491
Cable performance
Item Unit Multimode specification
Core/modal diameter mm 50.0±2.5 / 62.5±2.5
Cladding diameter mm 125.0±1.0
Maximum attenuation dB/km 3.5(@850nm);1.5(@1300nm)
Operating temperature -20~+85
Cable outer diameter mm 4.00±0.20
Permissible bending radius mm Dynamic 20D; static 10D
Tensile strength N Long-term 200; short-term 300
Crush strength N Long-term 800; short-term 1000
Marking information
  • Standard marking: Manufacturer info + Optic Fiber CABLE + MM 50/125 4.0mm + Fiber count + Month/Year + XXXXm
  • Custom marking content available per customer requirements.
Cable drum length
  • Standard drum lengths: 500m, 1000m, 2000m
  • 10% over/under shipment allowed; settlement based on actual shipped length.