| Technical Parameter Details | |
|---|---|
| Core Identification | Complies with international color standards |
| Conductor Resistance Standard | Complies with Class 5 of IEC60228 |
| Rated Voltage | 0.6/1KV |
| Insulation Resistance | >20MΩ x km (at 20℃) |
| Test Voltage | 4000V AC, 5 minutes |
| Temperature Range | Fixed installation: -20℃ to +80℃; occasional flexing: -10℃ to +80℃ |
| Minimum Bending Radius | Fixed installation: 4X cable diameter; occasional flexing: 8X cable diameter |
Delivery Standard